§ 9.52.180. Appendix B, Fire-Flow Requirements For Buildings, adopted and amended.  


Latest version.
  • International Fire Code, 2009 Edition, Appendix B, Fire-Flow Requirements For Buildings, is hereby adopted in its entirety with the following amendments:

    9.52.180.1 Section B105.3 Fire-Flow requirements for private fire hydrants, added. International Fire Code, 2009 Edition, Section B105.3 Fire-Flow requirements for private fire hydrants, is hereby added to read as follows:

    B105.3 Fire-Flow requirements for private fire hydrants. The minimum required Fire Flow for private fire hydrants shall be 1000 gallons per minute (gpm) for one hour duration.

    9.52.180.2 Section B105.4 Fire-Flow data, added. International Fire Code, 2009 Edition, Section B105.4 Fire-Flow data, is hereby added to read as follows:

    B105.4 Fire-Flow data. The water flow test data shall only be valid if the required data is obtained within three years from the date plans are submitted to the fire code official.

(Ord. No. 17423, 9-21-2010, eff. 1-1-2011)