§ 18.16.280. Section 600.43 Miscellaneous Provisions, added.
NFPA 70 National Electrical Code, 2014 Edition, Section 600.43 Miscellaneous Provisions, is hereby added to read as follows:
600.43 Miscellaneous Provisions.
(A) Sign circuits shall contain a copper grounding conductor deriving from the circuit's supply source; exterior locations shall terminate in a weatherproof box and cover. Taps in metallic raceways shall not be allowed as the grounding means.
(B) All sign installations shall maintain a clearance from adjacent power lines as follows:
Voltage—Line To Ground H (ft.)
Minimum Horizontal ClearanceV (ft.)
Minimum Clearance Measured Either Diagonally or VerticallyV (ft.)
Over or Under Catwalks Minimum Clearance Measured Either Diagonally or VerticallyGuy Wires and Neutrals 3 3 10.5 0—750 V Supply Cables Meeting Rule 230C2 and 230C3 NESC, 1997 3.5 3.5 11 0—750 V Open Conductors N.E.S.E. Rule 230C2 and 230C3 5.5 6 11.5 750V—22KV 7.5 8 13.5 Notes to table:
1.
Signs should never hang over any adjacent power circuits.
2.
Voltages are line to ground on a Y-Circuit with multi-ground neutral or between phases on an underground circuit.
(Ord. No. 18512 , § 1, 5-31-2016)