  • NFPA 70 National Electrical Code, 2014 Edition, Section 600.43 Miscellaneous Provisions, is hereby added to read as follows:

    600.43 Miscellaneous Provisions.

     (A) Sign circuits shall contain a copper grounding conductor deriving from the circuit's supply source; exterior locations shall terminate in a weatherproof box and cover. Taps in metallic raceways shall not be allowed as the grounding means.

     (B) All sign installations shall maintain a clearance from adjacent power lines as follows:

    Voltage—Line To Ground H (ft.)
    Minimum Horizontal Clearance
    V (ft.)
    Minimum Clearance Measured Either Diagonally or Vertically
    V (ft.)
    Over or Under Catwalks Minimum Clearance Measured Either Diagonally or Vertically
    Guy Wires and Neutrals 3 3 10.5
    0—750 V Supply Cables Meeting Rule 230C2 and 230C3 NESC, 1997 3.5 3.5 11
    0—750 V Open Conductors N.E.S.E. Rule 230C2 and 230C3 5.5 6 11.5
    750V—22KV 7.5 8 13.5

     

    Notes to table:

    1.

    Signs should never hang over any adjacent power circuits.

    2.

    Voltages are line to ground on a Y-Circuit with multi-ground neutral or between phases on an underground circuit.