§ 18.16.100. Section 230.43 Wiring Methods for 1,000 Volts, Nominal, or Less, amended.  


Latest version.
  • NFPA 70 National Electrical Code, 2008 Edition, Section 230.43 Wiring Methods for 600 Volts, Nominal, or Less, is hereby amended to read as follows:

    230.43 Wiring Methods for 1000 Volts, Nominal, or Less. Service entrance conductors shall be installed in accordance with the applicable requirements of this Code covering the wiring method used and shall be limited to the following wiring methods:

     (a) Rigid metal conduit

     (b) Intermediate metal conduit

     (c) Electrical metallic tubing

     (d) Busways

     (e) Metal wireways

     (f) Metal auxiliary gutters

     (g) Non-metallic rigid conduit for laterals only

     (h) Flexible metal conduit not over 6 feet (1.83 m) long or liquid tight flexible metal conduit not over 6 feet (1.83 m) long between raceways, or between raceway and service equipment, with equipment bonding jumper routed with the flexible metal conduit or the liquid tight flexible metal conduit according to the provisions of Section 250-102(a), (b), (c) and (e)

     (i) Liquid tight flexible nonmetallic conduit.

     (j) Mineral-insulated, metal-sheathed cable.

(Ord. No. 18512 , § 1, 5-31-2016)