§ 18.16.070. Section 215.13 Wiring Methods for Feeders 600 Volts or Less, added.  


Latest version.
  • NFPA 70 National Electrical Code, 2014 Edition, Section 215.13 Wiring Methods for Feeders 600 Volts or Less, is hereby added to read as follows:

    215.13 Wiring Methods for Feeders 600 Volts or Less.

     (a) All occupancies: Feeder conductors shall be installed in accordance with the applicable requirements of this Code covering the type of wiring method used and shall be limited to the following methods:

     (1) Rigid metal conduit

     (2) Intermediate metal conduit

     (3) Electrical metallic tubing

     (4) Busways

     (5) Metal wireways

     (6) Rigid non-metallic conduit

     (7) Mineral insulated, metal sheathed cable

     (8) Surface metal raceways

     (9) Cellular metal raceways

     (10) Cable bus

     (11) Flexible metal conduit only where one of the other methods cannot be reasonably installed and only if equipped with the appropriate size equipment ground conductor

     (12) Electrical non-metallic tubing

     (13) Metal clad cable

     (14) Armored cable

     (b) All one-family, two-family or multi-family occupancies:

     (1) All of the wiring methods listed in subparagraph (a) above

     (2) Underground feeder and branch circuit cable

     (3) Service entrance cable

     (4) Non-metallic sheathed cable

(Ord. No. 18512 , § 1, 5-31-2016)