§ 18.08.220. Section 3305.2 Temporary Facilities, added.
International Building Code, 2015 Edition, Section 3305.2 Temporary Facilities, is hereby added to read as follows:
3305.2 Temporary Facilities. Adequate sanitary facilities for the convenience of all workmen shall be provided according to Table 3305.1. Required facilities shall be located not more than one hundred (100) feet from the construction site, and shall not be within sixty (60) feet of any occupied structure, unless the occupant of such structure consents, or unless it is impracticable to locate the facilities the required minimum distance from the structure. Existing facilities owned by others may be used provided permission for their use is obtained and only if such facilities comply with the requirements or this section.
3305.3 Facilities shall be kept in a clean and sanitary condition throughout the duration of the work. The temporary workman's toilet shall be enclosed, screened, and weatherproofed and shall be connected to a sewer. Upon removal of the temporary facilities, the sewer connections shall be removed and the sewer capped. In lieu of connecting to a sewer, the temporary facility may be a portable, enclosed, chemically treated, tank-tight unit.
Table 3305.1 Number of Employees
Minimum Number of Toilet FacilitiesIf Serviced Once Per Week* 1—10 1 11—20 2 21—30 3 31—40 4 Over 40 1 additional facility
for each 10 additional
employeesIf serviced more than once per week* 1—15 1 16—35 2 36—55 3 56—75 4 76—95 5 Over 95 1 additional facility
for each 20 additional
employees*"Servicing" refers to the emptying of waste and the cleaning of the toilet facility. A camp equipped with flush toilets shall meet the standard for "minimum number of toilet facilities if serviced more than once per week".